Everexceed PXM Plus 10-90kW

The Everexceed 10-90kW UPS combines unprecedented efficiency, reliability, and vertical or horizontal scalability with eye-catching design. A space-saving, flexible device that’s  easy to deploy and manage, it’s the perfect three-phase power solutions for today small data center that offer lower cost of ownership.

Features:

  • True N+X Modular redundancy
  • High efficiency > 95%
  • 7 inches colour touch screen LCD
  • 3 level inverter technology
  • Up to 95 % operating efficiency (on-line mode)
  • Up to 98 % operating efficiency (Eco Mode)
  • Smart sleep function
  • 9 programmable relay contact as standard
  • 10 kVA  and 15kVA hot-swappable Power modules (2U high)
  • 20kva , 30kVA, 45kVA, 60kVA  and 90 kVA UPS frame sizes
  • Parallel up to 4 frames for additional resilience
  • UPS modules incorporate idle mode and cyclic operation
  • Output PF up to unity
  • Phase configuration options 1/1, 3/1 and 3/3
  • Centralized static and manual bypass lines
  • Centralized battery connection
  • Built-in Intelligent Test Mode
Category:

Description

TECHNICAL SPECIFICATION.
MODEL PXM 20kVA PXM 30kVA PXM 40kVA PXM 60kVA PXM 30kVA PXM 45kVA PXM 90kVA
Capacity 20kVA/kW 30kVA/kW 40kVA/kW 60kVA/kW 30kVA/kW 45kVA/kW 90kVA/kW
Power Module PM10X (10kVA/10kW) PM15X (15kVA/15kW)
INPUT
Input Voltage 1:1,3:1,3:3 manual selection at input terminal
Harmonic
Distortion
<4% @ 100% linear load
Voltage Range 304-478Vac (Line-Line),full load. 228V-304Vac (Line to Line)
Frequency 45Hz to 55Hz (auto detect)
Power Factor > 0.99
OUTPUT
Voltage 3 phase 415Vac, 220/230/240Vac- 1 phase
Frequency 50Hz / 60Hz ± 3Hz seletable
Waveform Pure sine wave
Accuracy +/- 1% static mode /  +/- 1.5% dynamic mode
Harmonic
Distortion
< 5% of T.H.D. at non-linear load
< 1% of T.H.D. at linear load
Efficiency 95% online mode, 94.5% battery mode, 98% ECO mode
Overload
Protection
Load<110%:60min, <125%:10min, <150%:1min, >150%:200ms
Short Circuit
Protection
UPS output cut off immediately or protected by input fuse or circuit breaker
Alarm Buzzer beeps under backup mode, battery low, fault and overload
BATTERY
Type Sealed, maintenance-free lead acid battery
Recharge time 6 – 8 hours to 90%
Battery +/- 240VDC
Runtime Extended runtime
Charging cycle Intelligent Battery Management, 3 level charging
PHYSICAL
Cabinet without
battery (kg)
42 55 51 85 42 55 85
Power Module (kg) 15.3 15.5
Cabinet (WxDxH)mm 485*751*398 (7U) 485*751*575 (11U) 485*751*1033 (21U) 485*751*398 (7U) 485*751*575 (11U) 485*751*1033 (21U)
Display LED and 7″colour touch screen
Installation Top or bottom cable entry
Protection IP20
Interface RS232, RS485, Dry contact, EPO, SNMP Card optional
Audible Noise < 55dBA (1m from surface)
Altitude <1500m
Ambient
Temperature
+0 °C to +40 °C
Storage
Temperature
-15 °C to +50 °C
Humidity 0-95%, non-condensing
STANDARD
Operation VFI-SS-111 as per EN/IEC62040-3
Quality Control ISO 9001, ISO 14001, CE, TUV
Safety IEC/EN62040-1
EMC IEC/EN62040-2
Note: Specification is subject to change without prior notice.